Self-supporting insulated (SIP) wires are intended for electric power transmission in overhead power lines and branches to inputs to residential buildings and outbuildings, rated for AC voltage 0.66 / 1 kV with a rated frequency of 50Hz. Wires self-supporting SIP are durable, capable of uninterrupted operation even in aggressive climatic and chemical conditions, they presume the possibility of mounting without disconnecting the line, high strength to mechanical damage, which is their essential technical advantages. The components of the wire and the cabling of the SIP wire can be presented in 4 parts. The conductor core is made of aluminum, it has a round shape, in the cross section of the wire - 16 - 150 sq. M. Bearing zero vein is formed from twisted round wires (multiwire), compacted, uninsulated, round shape. The material for its manufacture is aluminum alloy. Insulation of the core in the wires of SIP is made of thermoplastic light-stabilized cross-linked polyethylene. Twisting is a twisted conductive isolated veins around the zero carrier
SIP1
Self-supporting wires
Isolated and protected for overhead power lines
Applies to:
For highways of overhead transmission lines (OL) and linear branches from overhead lines in air of types I and II in accordance with GOST 15150.
-1. Aluminum compacted core
-2. Aluminium alloy
-3. Isolation from silanol-crosslinked PE
Characteristics: marks SIP1
1. The rated voltage is up to 0.6 / 1 kV.
2. Ambient temperature during cable operation from -50 ° C to + 50 ° C.
3. Relative air humidity up to 98% at a temperature of 35 ° C.
4. The minimum cable laying temperature without preliminary warming up is 20 ° С.
5. The long-term permissible operating temperature of the conductors is 90 ° C
6. The maximum permissible temperature of heating the cores of the cable in emergency mode is 130 ° С
7. The maximum temperature of heating of the veins with a short-circuit of 250 ° C
8. The minimum allowable bend radius when laying 10 wire diameters.
9. Service life is not less than 30 years.
Wire structure:
1. Aluminum core section 16-240 mm2.
2. The zero core is made of aluminum alloy.
3. Isolation from light-stabilized silanol-cross-linked polyethylene.
SIP2
Self-supporting wires
Isolated and protected for overhead power lines
Applies to:
For branches from the overhead line to the input and for laying on walls of buildings and engineering structures in air of types II and III according to GOST 15150.
-1. Aluminum compacted core
-2. Isolation from silanol-crosslinked PE
-3. Aluminium alloy
Characteristics: SIP 2
1. Rated voltage - up to 0,6 / 1 kV.
2. Ambient temperature during cable operation from -50 ° C to + 50 ° C.
3. Relative air humidity up to 98% at a temperature of 35 ° C.
4. The minimum temperature of cable laying without preheating is 20 ° С.
5. Approximate long-term permissible operating temperature of conductors 70 ° C
6. Maximum permissible temperature of cable conductor heating in emergency mode 80 ° C
7. Maximum temperature of heating the cores at a short-circuit of 135 ° C
8. The minimum permissible bending radius for laying 7.5 diameters of the wire
9. Service life is not less than 30 years.
Cable structure:
1. Stranded, sealed aluminum conductor. 16-240 mm2.
2. Insulation from light-stabilized silanol-cross-linked polyethylene.
3. Zero core - from aluminum alloy.
SIP3
Self-supporting wires
Isolated and protected for overhead power lines
Applies to:
For HVL, the nominal voltage of 10-35 kV in air of types II and III according to GOST 15150, including on the coasts of seas, saline lakes, in industrial areas and areas of saline sands.
-1. Aluminium alloy
-2. Isolation from silanol-crosslinked PE
Characteristics: SIP 3
1. Rated voltage -20 kV, 35 kV.
2. Ambient temperature during cable operation from -50 ° C to + 50 ° C.
3. Relative air humidity up to 98% at a temperature of 35 ° C.
4. The minimum temperature of cable laying without preheating is 20 ° С.
5. The long-term permissible operating temperature of the conductors is 70 ° С
6. The maximum allowable temperature of heating the cores of the cable in emergency mode 130 ° С
7. The maximum temperature of heating the cores at a short-circuit of 250 ° C
8. The minimum permissible bending radius when laying 10 diameters of the wire
9. Service life is not less than 30 years.
Cable structure:
1. A vein from an aluminum alloy.
2. Insulation from light-stabilized silanol-cross-linked polyethylene.
SIP4
Self-supporting wires
Isolated and protected for overhead power lines
Applies to:
For highways and linear branches from overhead lines in the atmosphere of air types II and III in accordance with GOST 15150, including on the coasts of seas, saline lakes, in industrial areas and areas of saline sands.
-1. Aluminum compacted core
-2. Isolation from silanol-crosslinked PE
Characteristics: SIP 4
1. Rated voltage - up to 0,6 / 1 kV.
2. Ambient temperature during cable operation from -50 ° C to + 50 ° C.
3. Relative air humidity up to 98% at a temperature of 35 ° C.
4. The minimum temperature of cable laying without preheating is 20 ° С.
5. The long-term permissible operating temperature of the conductors90 ° С
6. The maximum allowable temperature of heating the cores of the cable in emergency mode 130 ° С
7. The maximum temperature of heating the cores at a short-circuit of 250 ° C
8. The minimum permissible bending radius when laying 10 diameters of the wire
9. Service life is not less than 30 years.
Cable structure:
1. Stranded, sealed aluminum conductor. 16-240 mm2.
2. Insulation from light-stabilized silanol-cross-linked polyethylene.
Number and nominal cross-section of conductors, mm2 | Outer wire diameter, mm | Estimated weight of 1 km of wire / 1kg | Nominal insulation thickness |
SIP-4 2х16 | 17.2 | 142.6 | 1.3 |
SIP-4 2х25 | 19.8 | 205.5 | 1.3 |
SIP-4 3х16 | 15.7 | 206 | 1.3 |
SIP-4 3х25 | 18.1 | 292 | 1.3 |
SIP-4 4х16 | 20.08 | 285.3 | 1.3 |
SIP-4 4х25 | 23.9 | 410.9 | 1.3 |
SIP-4 4х35 | 27.1 | 544.7 | 1.3 |
SIP-4 4х50 | 30.9 | 730.8 | 1.5 |
SIP-4 4х70 | 35.6 | 1014.1 | 1.7 |
SIP-4 4х95 | 41.5 | 1358.5 | 1.7 |
SIP-4 4х120 | 45.2 | 1683.2 | 1.7 |